25IOB16 FAQ

remote control function question.

2pcs 25IOB16 modules.

I want to use both of them for input and output back and forth.

I can only set it so that each card input switches the outputs of the second card.

This is fine.

I would like it to work in reverse at the same time.

Can this be solved?

 

Another question:

This is related to all output cards.

If one or more outputs are active and the RS485 communication is interrupted, the outputs do not switch back to their default state.

I think this is a big source of danger.

I can't find it in the descriptions or is there no such option?

 

I'm waiting for your answer.

Have a nice day.

 

Jozsef

 

tbsteamkft@gmail.com

1  For two-way control, please set it as follows:
Demo : https://youtu.be/VAXZCPh-PwA

Set Up Remote IO:

Enable Remote IO Receiver: 01 06 00 F6 00 01 A8 38

Enable  Remote IO Sender : 01 06 00 F5 00 01 58 38

2 Remote IO is just an additional function of this board. It only has this simple controller mode and no hold function.

 

 

Back to blog

Leave a comment